iR2 Installation Manual Page 13 Software Revision1-0
- - -
LED Strobe / Lamp Output (Terminal 5)
An external LED Strobe/Lamp can be connected between Terminal 3 (anode +'ve) and Terminal 4 (cathode
-'ve). This 12V open-collector output mimics the internal LED Strobe/Lamp and is current limited to 20mA
with an on-board 220ohm resistor.
Relay Output (Terminal 6,7,8)
- Programmable Option
As supplied from the factory the relay operates as a Fire Alarm relay, but it can alternatively be programmed
to operate as a Fault Output Relay by keying the following sequence:
Engineer Access Code-1 Select Toggle Relay Option
LEDs Off= Fire Alarm Relay*
LEDs On= Fault Relay
* Factory default setting
Note that when programmed as a Fault Output the relay is normally in a de-energised state in
order to conserve standby battery power. Total power loss will therefore not be signalled to
external equipment.
The green Power LED flashes rapidly upon successfully entering the Engineer Access Code.
The LEDs surrounding button indicate the current option status.
Toggle button to set/unset the desired option.
Press to accept OR press to quit without updating the option.